Feeder_4 logic scheme, Normal operation - control, Normal operation - protection – Basler Electric BE1-851 User Manual
Page 191: Normal operation - reclosing, Feeder_4 logic scheme -35, Normal operation - control -35, Normal operation - protection -35, Normal operation - reclosing -35

SL-143 = 2
SL-243 = 2
SL-343 = 2
SL-101 = 1
SL-VOA = ALMMAJ
SL-VO1 = VO11+BFPU+101T
SL-VO2 = 79C+101C
SL-VO3 = IN4*/343
SL-VO4 = VO12*/VO5*IN4*/343
SL-VO5 = BFT
SL-VO6 = 0
SL-VO7 = 0
SL-VO8 = 0
SL-VO9 = /IN2+143+/101SC+VO5+150TPT+150TNT
SL-VO10 = VO11
SL-VO11 = 50TPT+50TNT+150TPT+150TNT+51PT+51NT
SL-VO12 = 50TPPU+50TNPU+150TPPU+150TNPU+51PPU+51NPU
SL-VO13 = 0
SL-VO14 = 0
SL-VO15 = /IN4+343
Feeder_4 Logic Scheme
Logic scheme Feeder_4 is meant for use on a feeder breaker and provides all overcurrent and breaker
failure protection, reclosing, and control functions required for a typical feeder in a non-directional
overcurrent protection application. This logic is intended for use in conjunction with redundant protective
relays such as existing electromechanical relays to provide backup when the relay is out of service.
Automatic reclosing is initiated by the breaker opening. Reclosing is disabled after a manual trip by a
control switch slip contact. In this logic scheme, the disable logic is connected to the reclose initiate (RI)
input. Once re-enabled, the recloser will start the sequence and automatically close the breaker if it is
open.
When used in conjunction with other programmable relays using logic scheme BUS, it can provide
complete overcurrent protection for the transformers, bus, and feeders in a radial system substation.
The components of Feeder_4 logic are summarized in Tables 8-17 through 8-20. Figure 8-9 is a one-line
diagram of Feeder_4 logic and Figure 8-10 is a diagram representing the logic settings and equations of
Feeder_4 logic.
Normal Operation - Control
The virtual breaker control switch is programmed to provide manual trip and close control of the breaker.
The control functions of this logic scheme use both traditional contact sensing inputs and virtual switches.
Virtual switches that are not needed may simply go unused. The protection engineer may choose to free
up contact sensing inputs for other uses by using the virtual switches exclusively for the various control
functions.
Normal Operation - Protection
The 50T and 51 function blocks and the breaker failure function block re-trip output are enabled in
Feeder_4 logic for tripping via OUT1. Setting the pickup at zero in the four setting groups can individually
disable each overcurrent function block.
The 50TN, 50TQ, 51N, and 51Q function blocks are torque controlled by Virtual Switch 243. All N and Q
function blocks or only the 51N and 51Q function blocks may be inhibited. This is done in BESTlogic by
modifying the inputs to the function blocks.
Normal Operation - Reclosing
The reclosing logic in Feeder_4 is initiated by the breaker opening. Automatic reclosing is disabled for a
manual trip by a control switch slip contact. Setting the first reclose time = zero can disable the recloser
function block in the four setting groups.
9289900990 Rev R
BE1-851 Application
8-35