Metering commands, Report commands, Metering commands -9 – Basler Electric BE1-851 User Manual
Page 251: Report commands -9

EXIT Command
Purpose:
Exit programming mode
Syntax:
EXIT - Note: Relay will prompt for verification
Example:
EXIT
Reference:
Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
HELP Command
Purpose:
Obtain help on command operation
Syntax:
HELP {cmd} or H {cmd} for help on {cmd}, H1 for command list
Example:
HELP, H1, H SG-COM
Reference:
Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
Metering Commands
M Command
Purpose:
Read all metered values
Syntax:
M
Example:
M
Reference:
Section 5, Metering
M-I Command
Purpose:
Read metered current (I) in primary units
Syntax:
M-I[{phase}] where phase = A/B/C/N/Q
Example:
M-I or M-IA or M-IN
Reference:
Section 5, Metering
Report Commands
RA Command
Purpose:
Report/Reset Alarm information
Syntax:
RA[=0]
Example:
RA
Reference:
Section 6, Reporting and Alarms, Alarms Function
RA-MAJ Command
Purpose:
Report/Reset Major Alarm information
Syntax:
RA-MAJ[=0]
Example:
RA-MAJ
Reference:
Section 6, Reporting and Alarms, Alarms Function
RA-MIN Command
Purpose:
Report/Reset Minor Alarm information
Syntax:
RA-MIN[=0]
Example:
RA-MIN
Reference:
Section 6, Reporting and Alarms, Alarms Function
RA-REL Command
Purpose:
Report/Reset Relay Alarm information
Syntax:
RA-REL[=0]
Example:
RA-REL
Reference:
Section 6, Reporting and Alarms, Alarms Function
9289900990 Rev R
BE1-851 ASCII Command Interface
11-9