Time dial setting cross-reference, Using table a-3 – Basler Electric BE1-851 User Manual
Page 333
Table A-2. Characteristic Curve Cross-Reference
Curve
Curve Name
Similar To
S1
Short Inverse
ABB CO-2
S2
Short Inverse
GE IAC-55
L1
Long Inverse
ABB CO-5
L2
Long Inverse
GE IAC-66
D
Definite Time
ABB CO-6
M
Moderately Inverse
ABB CO-7
I1
Inverse Time
ABB CO-8
I2
Inverse Time
GE IAC-51
V1
Very Inverse
ABB CO-9
V2
Very Inverse
GE IAC-53
E1
Extremely Inverse
ABB CO-11
E2
Extremely Inverse
GE IAC-77
A
Standard Inverse
Refer to BS 142
B
Very Inverse (I
2
t)
Refer to BS 142
C
Extremely Inverse (I
2
t)
Refer to BS 142
G
Long Time Inverse (I
2
t)
Refer to BS 142
F
Fixed Time
N/A
P
Programmable
N/A
Time Dial Setting Cross-Reference
Although the time characteristic curve shapes have been optimized for each relay, time dial settings of
Basler Electric relays are not identical to the settings of electromechanical induction disk overcurrent
relays. Table A-3 helps you convert the time dial settings of induction disk relays to the equivalent setting
for Basler Electric relays. Enter time dial settings using BESTCOMS™, S
commands, or at human-machine interface (HMI) Screens 5.x.4.1 (51P), 5.x.4.2 (51N), and 5.x.4.3 (51Q)
for “H” style relays. For “G” style relays use HMI Screens 5.x.4.1 (51P), 5.x.4.2 (51N), and 5.x.4.3 (151N).
For more information, refer to Section 4, Protection and Control, Overcurrent Protection, 51 - Time
Overcurrent Protection.
Using Table A-3
Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial
calculator function for each time dial setting. The equivalent Basler Electric time dial setting was then
entered into the cross-reference table.
If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electromechanical setting
and the Basler Electric setting.
Basler Electric relays have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial
setting for the electromechanical maximum setting is provided in the cross-reference table even if it
exceeds 9.9. This allows interpolation as noted above.
Basler Electric time current characteristics are determined by a linear mathematical equation. The
induction disk of an electromechanical relay has a certain degree of non linearity due to inertial and
friction effects. For this reason, even though every effort has been made to provide characteristic curves
with minimum deviation from the published electromechanical curves, slight deviations can exist between
them.
In applications where the time coordination between curves is extremely close, we recommend that you
choose the optimal time dial setting by inspection of the coordination study. In applications where
9289900990 Rev R
BE1-851 Time Overcurrent Characteristic Curves
A-3