Timings, 50t timings, Timings -7 – Basler Electric BE1-851 User Manual
Page 295: 50t timings -7, Table 13-14. pickup settings -7, Table 13-15. pickup ranges -7, N table 13-14

Table 13-14. Pickup Settings
Style Number
Commands
Phase
Neutral
x1xxxxx
S0-51P=3.2A,0m
S0-51N=3.2A,0m
x3xxxxx
S0-51P=16.0A,0m
S0-51N=3.2A,0m
x5xxxxx
S0-51P=16.0A,0m
S0-51N=16.0A,0m
Step 9:
Slowly ramp up the current applied at the relay Phase A input until OUT1 closes. Verify that
pickup occurred within the acceptable range listed in Table 13-15.
Table 13-15. Pickup Ranges
Style
Number
Phase
Neutral
Low Limit
High Limit
Low Limit
High Limit
x1xxxxx
3.136 amps
3.264 amps
3.136 amps
3.264 amps
x3xxxxx
15.68 amps
16.32 amps
3.136 amps
3.264 amps
x5xxxxx
15.68 amps
16.32 amps
15.68 amps
16.32 amps
Step 10:
After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur
at 95% ±2% of the pickup current magnitude.
Step 11:
Repeat Steps 2 through 10 for the Phase B current input.
Step 12:
Repeat Steps 2 through 10 for the Phase C current input.
Step 13:
Repeat Steps 2 through 10 for the Neutral current input.
Timings
50T Timings
Step 1:
Transmit the following scheme to the relay:
ACCESS=851
SL-N=NONE
YES
SL-N=TIME50
SL-50T=1,0
SL-VO1=50TPT+50TNT
SG-DSP=F
EXIT;Y
Step 2:
Transmit the appropriate command in Table 13-16 to program the pickup and timer settings.
9289900990 Rev R
BE1-851 Testing and Maintenance
13-7