51 pickups and dropouts, 51 pickups and dropouts -5, Table 13-8. pickup settings -5 – Basler Electric BE1-851 User Manual
Page 293: Table 13-9. pickup ranges -5

Step 7:
After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur
at 90% ±2% of the pickup current magnitude.
Step 8:
Transmit the appropriate command in Table 13-8 to reprogram the pickup setting.
Table 13-8. Pickup Settings
Style Number
Commands
Phase
Neutral
x1xxxxx
S0-50TP=5.0A,0m
S0-50TN=5.0A,0m
x3xxxxx
S0-50TP=25.0A,0m
S0-50TN=5.0A,0m
x5xxxxx
S0-50TP=25.0A,0m
S0-50TN=25.0A,0m
Step 9:
Slowly ramp up the current applied at the relay Phase A input until OUT1 closes. Verify that
pickup occurred within the acceptable range listed in Table 13-9.
Table 13-9. Pickup Ranges
Style
Number
Phase
Neutral
Low Limit
High Limit
Low Limit
High Limit
x1xxxxx
4.9 amps
5.1 amps
4.9 amps
5.1 amps
x3xxxxx
24.5 amps
25.5 amps
4.9 amps
5.1 amps
x5xxxxx
24.5 amps
25.5 amps
24.5 amps
25.5 amps
Step 10:
After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur
at 90% ±2% of the pickup current magnitude.
Step 11:
Repeat Steps 2 through 10 for the Phase B current input.
Step 12:
Repeat Steps 2 through 10 for the Phase C current input.
Step 13:
Repeat Steps 2 through 10 for the Neutral current input.
51 Pickups and Dropouts
Step 1:
Transmit the following scheme to the relay:
ACCESS=851
SL-N=NONE
YES
SL-N=PU51
SL-51=1,0
SL-VO1=51PT+51NT
EXIT;Y
Step 2:
Transmit the appropriate command in Table 13-10 to program the pickup setting.
9289900990 Rev R
BE1-851 Testing and Maintenance
13-5