Operating settings for setting group control, Operating settings for setting group control -5, Figure 4-4. input control binary inputs -5 – Basler Electric BE1-851 User Manual
Page 61: Figure 4-5. setting group selection screen -5, Figure 4-4

Figure 4-4. Input Control Binary Inputs
Example 1. Make the following settings changes to the setting group control function. Set the setting
group control such that automatic selection is overridden and emergency overload
settings (SG3) are in place when transformer 2 is out of service. Contact Sensing Input 2
is TRUE when either the high side or low side breakers for Transformer 2 are open. Refer
to Figure 4-2 for an example.
Mode:
Binary Inputs
D0:
Connect to IN2
D1:
Connect to IN2
D2:
Connect to 0
D3:
Connect to 0
Automatic:
Connected to /IN2
Operating Settings for Setting Group Control
Operating settings can be made using BESTCOMS. Figure 4-5 illustrates the BESTCOMS screen used to
select operational settings for the Setting Group Control function. To open the Setting Group Selection
screen, select Setting Group Selection from the Screens pull-down menu. Alternately, settings can be
made from the ASCII command interface using the SG-SGCON (settings general-SGC Alarm on time)
command.
Figure 4-5. Setting Group Selection Screen
9289900990 Rev R
BE1-851 Protection and Control