Table 13-19. timing ranges -9, Table 13-20. pickup settings -9, Table 13-21. pickup ranges -9 – Basler Electric BE1-851 User Manual
Page 297

Table 13-19. Timing Ranges
Style
Number
Current/Frequency
Timing Range
Phase
Neutral
Low Limit
High Limit
x1xxxxx
5.0A/50 Hz
5.0A/50 Hz
0.0 sec
0.025 sec
x1xxxxx
5.0A/60 Hz
5.0A/60 Hz
0.0 sec
0.021 sec
x3xxxxx
25.0A/50 Hz
5.0A/50 Hz
0.0 sec
0.025 sec
x3xxxxx
25.0A/60 Hz
5.0A/60 Hz
0.0 sec
0.021 sec
x5xxxxx
25.0A/50 Hz
25.0A/50 Hz
0.0 sec
0.025 sec
x5xxxxx
25.0A/60 Hz
25.0A/60 Hz
0.0 sec
0.021 sec
Step 6:
Transmit the appropriate command in Table 13-20 to program the pickup setting.
Table 13-20. Pickup Settings
Style Number
Commands
Phase
Neutral
x1xxxxx
S0-50TP=1.0A,5s
S0-50TN=1.0A,5s
x3xxxxx
S0-50TP=5.0A,5s
S0-50TN=1.0A,5s
x5xxxxx
S0-50TP=5.0A,5s
S0-50TN=5.0A,5s
Step 7:
Apply the appropriate current value to the Phase A input and measure the time between the
application of current and OUT1 closing. Verify that the timing is within the acceptance range
stated in Table 13-21.
Table 13-21. Pickup Ranges
Style
Number
Current/Frequency
Timing Range
Phase
Neutral
Low Limit
High Limit
x1xxxxx
1.05A/50 Hz
1.05A/50 Hz
4.85 sec
5.35 sec
x1xxxxx
1.05A/60 Hz
1.05A/60 Hz
4.833 sec
5.333 sec
x3xxxxx
5.25A/50 Hz
1.05A/50 Hz
4.85 sec
5.35 sec
x3xxxxx
5.25A/60 Hz
1.05A/60 Hz
4.833 sec
5.333 sec
x5xxxxx
5.25A/50 Hz
5.25A/50 Hz
4.85 sec
5.35 sec
x5xxxxx
5.25A/60 Hz
5.25A/60 Hz
4.833 sec
5.333 sec
Step 8:
Repeat Steps 2 through 7 for the Phase B input.
Step 9:
Repeat Steps 2 through 7 for the Phase C input.
Step 10:
Repeat Steps 2 through 7 for the Neutral input.
9289900990 Rev R
BE1-851 Testing and Maintenance