Basler Electric BE1-851 User Manual
Page 205

Output
Purpose
Description
Label
State Labels
True
False
VO5
(OUT5)
Feeder breaker trip.
Trip feeder breaker via auxiliary
relay (94) for time (51) and
instantaneous (50T with 2-4
cycles delay) when in feeder
relay backup mode and not in
test mode.
BKR_FAIL
TRIP
NORMAL
BESTlogic Expression: VO5=VO11*SG1*/VO15
VO6
N/A
N/A
VO6
TRUE
FALSE
BESTlogic Expression: VO6=0
VO7
N/A
N/A
VO7
TRUE
FALSE
BESTlogic Expression: VO7=0
VO8
Time overcurrent trip.
TRUE if any of the time
overcurrent elements trip.
51_TRIP
TRIP
NORMAL
BESTlogic Expression: VO8=51PT+51NT+51QT
VO9
Instantaneous overcurrent
trip.
TRUE if any of the instantaneous
overcurrent elements trip.
50_TRIP
TRIP
NORMAL
BESTlogic Expression: VO9=50TPT+50TNT+50TQT
VO10
N/A
N/A
VO10
TRUE
FALSE
BESTlogic Expression: VO10=0
VO11
Protective Trip
Expression.
TRUE when any 50 or 51
element times out.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11=50TPT+50TNT+50TQT+51PT+51NT+51QT
VO12
Protection Pickup Up
Expression.
TRUE when any 50 or 51
element picks up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU
VO13
Relay is in feeder backup
mode.
TRUE if in setting group 1.
FEEDER_BU BACKUP NORMAL
BESTlogic Expression: VO13=SG1
VO14
N/A
N/A
VO14
TRUE
FALSE
BESTlogic Expression: VO14=0
VO15
The relay is in test mode,
breaker failure is
disabled, and reclosing is
disabled.
TRUE if IN4 is de-energized or if
Virtual Switch 343 is closed.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15=/IN4+343
9289900990 Rev R
BE1-851 Application
8-49