Basler Electric BE1-851 User Manual
Page 212

Output
Purpose
Description
Label
State Labels
True
False
VO11
Protective Trip
Expression.
TRUE when any 50 or 51
element times out.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11=50TPT+50TNT+50TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression.
TRUE when any 50 or 51
element picks up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU
VO13
N/A
N/A
VO13
TRUE
FALSE
BESTlogic Expression: VO13=SG1
VO14
N/A
N/A
VO14
TRUE
FALSE
BESTlogic Expression: VO14=0
VO15
The relay is in test mode,
breaker failure is
disabled, and reclosing is
disabled.
TRUE if IN4 is de-energized or
if Virtual Switch 343 is closed.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15=/IN4+343
8-56
BE1-851 Application
9289900990 Rev R