Table 8-27. backup virtual switch logic -54 – Basler Electric BE1-851 User Manual
Page 210

Function
Purpose
BESTlogic
Expression
Mode
Setting
51P
Used for timed phase overcurrent protection.
0
1 (enabled)
51N
Used for timed neutral overcurrent protection.
0
1 (enabled)
51Q
Used for timed negative-sequence overcurrent
protection.
0
1 (enabled)
62
N/A
0
0 (disabled)
162
N/A
0
0 (disabled)
79
N/A
0
0 (disabled)
BF
Initiate breaker failure when breaker failure initiate
expression is TRUE.
VO10
1 (enabled)
Block breaker failure protection when relay is in test
mode.
VO15
GROUP
Switch to setting group 1 if feeder relay is out of
service as indicated by open contact from feeder
relays.
/IN2
2(Binary
Inputs)
No manual logic is used.
0
No manual logic is used.
0
No manual logic is used.
0
Fix Auto/Manual switch in the manual position only.
Selection by contact sensing only. No automatic
selection logic.
0
Table 8-27. BACKUP Virtual Switch Logic
Switch
Purpose
Mode
Label
State Labels
True
False
43
N/A
0 (Disable)
SWITCH_43
CLOSED
OPEN
143
N/A
0 (Disable) SWITCH_143
CLOSED
OPEN
243
N/A
0 (Disable) SWITCH_243
CLOSED
OPEN
343
Put the relay in test mode so
that reclosing and breaker
failure are disabled when virtual
switch is closed.
2 (On/Off) TESTENABLE
TSTMODE
NORMAL
101
Virtual Control Switch to trip bus
breaker.
1 (Enable)
N/A
N/A
N/A
8-54
BE1-851 Application
9289900990 Rev R