Basler Electric BE1-851 User Manual
Page 258

SL-101 Command
Purpose:
Read/Set Logic for Virtual Breaker switch (101)
Syntax:
SL-101[=mode] where mode=0/1 (disabled/enabled)
Example:
SL-101 or SL-101=0 or SL-101=1
Reference:
Section 4, Protection and Control, Virtual Switches
SL-43 Command
Purpose:
Read/Set Logic for Virtual switch (x43)
Syntax:
SL-{x}43[=mode] where x = blank/1/2/3, mode=0/1/2/3
Example:
SL-43 or SL-143=0 or SL-243=1
Reference:
Section 4, Protection and Control, Virtual Switches
SL-50T Command
Purpose:
Read/Set Logic for x50 Function Modules where x = blank or 1
Syntax:
SL-x50T[{p}[={mode},{BLK logic}]] where p = P/N/Q and mode = 0/1/2
Example:
SL-50T or SL-50T=1,0 or SL-150TN=1,IN3
Reference:
Section 4, Protection and Control, Overcurrent Protection
SL-51 Command
Purpose:
Read/Set Logic for x51 Function Modules
Syntax:
SL-x51[{p}[={mode},{BLK logic}]] where p=P/N/Q
Example:
SL-51 or SL-51P=1,0 or SL-51N=1,IN3
Reference:
Section 4, Protection and Control, Overcurrent Protection
SL-62 Command
Purpose:
Read/Set Logic for 62 Function Modules
Syntax:
SL-{f}62[={mode},{INI logic},{BLK logic}] where f= 0/1
Example:
SL-62 or SL-62=1,VO10,0 or SL-162=2,VO9,VO8
Reference:
Section 4, Protection and Control, General Purpose Logic Timers (62/162)
SL-79 Command
Purpose:
Read/Set for 79 Function
Syntax:
SL-79[={mode},{RI logic},{STATUS logic},{WAIT logic},{LOCKOUT logic}]
Example:
SL-79 or SL-79=1,VO1+IN4,/IN1,IN2,IN3
Reference:
Section 4, Protection and Control, Reclosing
SL-BF Command
Purpose:
Read/Set Logic for Breaker Failure Function Modules
Syntax:
SL-BF[{p}[={mode},{INI logic},{BLK logic}]]
Example:
SL-BF or SL-BF=1,VO1,0 or SL-BF=1,VO1,IN1
Reference:
Section 4, Protection and Control, Breaker Failure Protection
SL-GROUP Command
Purpose:
Read/Set Logic for Setting Group Module
Syntax:
SL-GROUP[={mode},{D0logic},{D1logic},{D2logic},{D3logic},{AUTOlogic}]
Example:
SL-GROUP or SL-GROUP=1,IN3,IN4,0,0,0
Reference:
Section 4, Protection and Control, Setting Groups
SL-N Command
Purpose:
Read/Set Name of the custom logic
Syntax:
SL-N[={name}]
Example:
SL-N=851TEST
Reference:
Section 7, BESTlogic™ Programmable Logic, Logic Schemes
11-16
BE1-851 ASCII Command Interface
9289900990 Rev R