Virtual outputs – Basler Electric BE1-851 User Manual
Page 323

Figure 14-24. BESTlogic Screen, Logic Select Tab
Virtual Outputs
You can assign a meaningful name or label to each virtual output. This makes sequential events reports
easier to analyze. To assign a meaningful label to Virtual Output VO6, click in the Label field and enter
the new name. Refer to Figure 14-25. Remember, VO6 does not have actual hardware output contacts.
Only VOA and VO1 through VO5 have hardware output contacts. To change the label for the True State,
click on the True State field and enter the new name. To change the label for the False State, click on the
False State field and enter the new name. To change the logic associated with VO6, click on the
BESTlogic button associated with VO6. Click on the logic input and program the logic variables that
define VO6. You may clear the existing programming by clicking on the Clear button or clicking on each
individual variable. The other 15 virtual outputs have the same function.
Figure 14-25. BESTlogic Screen, Virtual Outputs Tab
9289900990 Rev R
BE1-851 BESTCOMS™ Software
14-19