ASCII Command
Function
HMI Screen
RB-OPCNTR[={#operations}]
Read/Set breaker operation counter.
4.3.1
RD
Report all demand data.
N/A
RD-PI[{p}[=0]]
Read/Reset peak demand current.
4.4.3.1 -
4.4.3.5
RD-TI[{p}]
Report today’s demand current.
4.4.1.1 -
4.4.1.5
RD-YI[{p}]
Report yesterday’s demand current.
4.4.2.1 -
4.4.2.5
RF[-n/NEW][=0]
Read/Reset fault report data.
N/A
RG
Report general information.
N/A
RG-DATE[={M/D/Y}] or RG-DATE[={D-M-Y}]
Read/Set date.
4.5
RG-DST
Report Start/Stop Times and Dates for
Daylight Savings Time referenced to local
time.
N/A
RG-STAT
Report relay status.
N/A
RG-TARG[=0]
Report/Reset target status.
1.2
RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn
Report/Set time.
4.5
RG-VER
Read program version, model number,
style number, and serial number.
4.6
RO-nA/B[#].CFG/DAT/HDR
Read Oscillographic COMTRADE Fault
Report.
N/A
RS[-n/Fn/ALM/IO/LGC/NEW][=0]
Read/Reset Sequence of Events Record
Data.
N/A
Table B-5. Setting Command
ASCII Command
Function
HMI Screen
S
Read all relay setting parameters.
N/A
Table B-6. Alarm Setting Commands
ASCII Command
Function
HMI Screen
SA
Read all major and minor alarm setting.
N/A
SA-BKR[n][={mode},{alarm limit}]
Read/Set breaker alarm settings.
N/A
SA-DI[p][={alarm level}]
Read/Set demand alarm settings.
N/A
SA-LGC[={alarm num 1}[/{alarm num 2}]...
[/{alarm num n}]]
Read/Set logic alarm setting mask.
N/A
SA-MIN[={alarm num 1}[/{alarm num 2}]...
[/{alarm num n}]]
Read/Set minor alarm setting mask.
N/A
SA-MAJ[={alarm num 1}[/{alarm num 2}]...
[/{alarm num n}]]
Read/Set major alarm setting mask.
N/A
SA-RESET[={rst alm logic}]
Read/Set programmable alarms reset
logic.
N/A
Table B-7. General Setting Commands
ASCII Command
Function
HMI Screen
SG
Read all general settings.
N/A
SG-CLK[={date format(M/D)},{time format(12/24)},
{dst enable(0/1)}]
Read/Program time and date format.
N/A
SG-COM[#[={baud},A{addr},P{pglen},
R{reply ack},X{XON ena}]]
Read/Set serial communication protocol.
6.1.1 - 6.1.3