Basler Electric BE1-851 User Manual
Page 187
![background image](https://www.manualsdir.com/files/773789/content/doc187.png)
Output
Purpose
Description
Label
State Labels
True
False
VO5
(OUT5)
Breaker failure trip
contact.
Trip backup if breaker failure
protection times out.
BKR_FAIL
TRIP
NORMAL
BESTlogic Expression: VO5=BFT
VO6
None
N/A
VO6
TRUE
FALSE
BESTlogic Expression: VO6=0
VO7
None
N/A
VO7
TRUE
FALSE
BESTlogic Expression: VO7=0
VO8
None
N/A
VO8
TRUE
FALSE
BESTlogic Expression: VO8=0
VO9
Recloser drive to lockout
expression.
Drive recloser to lockout to
disable it when IN2 is de-
energized or Virtual Switch
143 is closed or when the
breaker virtual control switch is
in the after trip state or if the
breaker fails or when the high
set instantaneous element
trips.
RCL_DTL
DTL
NORMAL
BESTlogic Expression: VO9=/IN2+143+VO5+150TPT+150TNT+150TQT
VO10
Breaker failure initiate
expression.
Initiate breaker failure timing
when protective trip expression
is TRUE.
BFI
INI
NORMAL
BESTlogic Expression: VO10=VO11
VO11
Protective Trip
Expression.
TRUE when any 50, 150, or 51
element times out.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11=50TPT+50TNT+50TQT+150TPT+150TNT+150TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression.
TRUE when any 50, 150, or 51
element picks up.
PROT_PU
PU
NORMAL
BESTlogic Expression:
VO12=50TPPU+50TNPU+50TQPU+150TPPU+150TNPU+150TQPU+51PPU+51NPU+51QPU
VO13
Alarm Mask 21.
N/A
VO13
TRUE
FALSE
BESTlogic Expression: VO13=0
VO14
Alarm Mask 22.
N/A
VO14
TRUE
FALSE
BESTlogic Expression: VO14=0
VO15
Alarm bit #23 indication
that the relay is in test
mode, breaker failure is
disabled, and reclosing is
disabled.
TRUE if IN4 is de-energized or
if Virtual Switch 343 is closed.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15=/IN4+343
9289900990 Rev R
BE1-851 Application
8-31