Implementation of stop categories

4

Function Description

Wiring suggestion

Implementation of Category 2 E-STOP, control function with auxiliary

contactors

Fig. 4-21:

Stop Category 2

][Funktion_Stopp_Motorleistung

`

S1: On

`

S2: Off

`

S3: E-STOP

Motor output P

M

Motor circuit brake resistor R

M

Up to 2.5 kW

27

Ω

(20 W) 1000 V

2.5 kW - 5 kW

8.2

Ω

(50 W) 1000 V

or

S1

S2

S3

BTB