beautypg.com

7commissioning, 5 messages/errors – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual

Page 187

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-15

7.5

Messages/errors

7

Commissioning

* from firmware V5.xx: These error messages must be reset with

DRVCNFG3 = 16. All other error messages can be cleared without a

hardware reset using the CLRFAULT parameter.

F17*

A/D Converter

Error in the analogue/digital conversion, often
caused by very strong electromagnetic inter-
ference

F18*

Brake chopper

Brake circuit defective or incorrect setting

F19

Intermediate circuit

Voltage drop in the intermediate circuit

F20*

Expansion card error

Slot error, depends on the expansion card
that's used, see ASCII command reference

F21*

Handling error

Handling error on the expansion card

F22

Reserved

Reserved

F23*

CAN Bus off

Major CAN Bus communication error

F24

Warning

Warning indicator assessed as an error

F25*

Commutation error

Commutation error

F26

Limit switch

Reference run error (hardware limit switch
reached)

F27*

STO

Operational error with STO, STO-ENABLE and
ENABLE inputs set simultaneously

F28

Fieldbus error

See also: ASCII command reference

F29

Fieldbus error

Communication disrupted, see ASCII com-
mand reference

F30

Emergency timeout

Timeout E-STOP

F31

Safety card error

Safety card's reaction monitoring is register-
ing an error.

F32*

System error

System software responds incorrectly

No.

Error message

Description