4.6

Implementation of stop categories

4

Function Description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-62

P

M

= (M

0

* n

n

) / 9550

where:

`

P

M

: Motor output [kW]

`

M

0

: Standstill torque [Nm]

`

n

n

: Rated speed [1/min]

4.6.3

Stop Category 2

Stop Category 2

4-

][Funktion_Stopp_2

The machine receives the operational stop command (disable) and

brakes the drive using the set braking ramp (STOPMODE and ACT-

FAULT parameters set to “1”).

`

The drive is braked in a controlled manner as it comes to a stop. If the

speed VEL0 (see timing diagram in the section entitled “Switch on/

switch off behaviour”) drops below the set value, the holding brake is

applied and the inverted rectifier is shut down. In this case, the mains

voltage is maintained.

`

If the mains is switched off, not only is a controlled braking procedure

initiated but the mains voltage is galvanically isolated from the holding

brake after a delay, which can be set on the timer.

5 kW - 10 kW

2.7

Ω

(110 W) 1000 V

10 kW - 20 kW

1

Ω

(300 W) 1000 V

20 kW - 40 kW

0.33

Ω

(600 W) 1000 V

Motor output P

M

Motor circuit brake resistor R

M