beautypg.com

Emc-compliant wiring, 1 earthing, 6wiring – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual

Page 115: 5 emc-compliant wiring

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-11

6.5

EMC-compliant wiring

6

Wiring

6.5

EMC-compliant wiring

6500

EMC-compliant wiring

6-

][EMV_Allgemein

In terms of electromagnetic compatibility (EMC), the servo amplifier

meets the requirements of the following standards and laws:

`

The EMC Directive 2004/108/EC

`

The Low Voltage Directive 2006/95/EC

`

The EMC product standard EN 61800-3, which contains limit values

and test methods for noise emission and immunity for adjustable

speed electrical power drive systems (PDS):

– Noise immunity: "Second environment" category (industrial envi-

ronment)

– Noise emission:

Category C2 (length of motor cable

10 m)

Category C3 (length of motor cable

10 m)

Measures for ensuring the wiring is EMC-compliant are:

`

Earthing

`

Shielding

`

Filters

`

Chokes

][EMV_Wohnumgebung

6.5.1

Earthing

Earthing

6-

][EMV_Erdung

Earthing measures are a prerequisite for the effective use of additional

EMC measures such as shielding or filters:

`

All earthing points should be fed directly to the central earth bar (equi-

potential bonding bar).

`

The connections must be low impedance and must be good conduc-

tors.

`

Connections should be kept as short as possible.

`

Connections to the earth bar should always be in star form.

`

Connections should be protected from corrosion.

`

Flexible earthing straps should be used on moving earth parts (e.g.

machine parts, gates). Ensure these earthing straps are as short and

wide as possible.

`

Unused wires in a cable should be earthed at both ends.

WARNING!

In a residential environment this product may cause high-fre-

quency noise, so that suppression measures may be required.