6 communications interfaces, 1 rs 232 interface, 6wiring – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual

Page 156: 7 control element

background image

6.7

Control element

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-52

6.7.6

Communications interfaces

Communications interfaces

6-

6.7.6.1

RS 232 interface

RS 232 interface

6-

][Verdr_RS_232_protego_D

We recommend shielded cable for the RS 232 interface.

If you use unshielded cables, the interface may malfunction.

`

Earth the cable shield connection at both ends (e.g. on a bus bar).

`

Transient currents can be anticipated on longer cables. If this is the

case you should use equipotential bonding cables.

`

With the supply voltages switched off, connect the interface (X6) on

the servo amplifier to a serial interface on the PC via a null modem ca-

ble.

INFORMATION

Do not use a null modem link cable!

Connector pin assignment

Connector X6

Pin

Designation

Description

2

RxD

Receive data

3

TxD

Send data

5

GND

Earth

Connection

Interface

RS 232

Shielded cable

Shield connection on a bus bar

The interface is on the same connec-
tor as the CANopen interface.

The RS 232 and CANopen interface
use the same operating earth (GND).

1

5

6

9

RxD

2

3

PMCprotego

X6

TxD

PC

5

GND

TxD

RxD

GND