beautypg.com

6wiring, 7 control element – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual

Page 127

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-23

6.7

Control element

6

Wiring

PMCprotego D without a safety card

Input circuit

Digital input: STO1-ENABLE/STO2-
ENABLE

Single-channel

24 VDC

Referenced to earth: Always con-
nect XGND (X4B/5) to I/O-GND on
the control system

Connect a safe semiconductor out-
put or positive-guided relay contact

Dual-channel

24 VDC

Referenced to earth: Always con-
nect XGND (X4B/5) to I/O-GND on
the control system

Connect the feedback signal for the
state of the pulse disabler to a digital
ouput (e.g. X3A/6)

If a safety function STO is not re-
quired:

Connect 24 VDC

Referenced to earth: Always con-
nect XGND (X4B/5) to I/O-GND on
the control system

3

IO-GND

XGND

6

PMCprotego D

X4A/B

STO1-ENABLE

5

STO2-ENABLE

24 V

3

IO-GND

XGND

6

PMCprotego D

X4A/B

STO1-ENABLE

5

STO2-ENABLE

24 V

X3A

DIGITAL-INOUT1

Ix

STO-Feedback

6

3

IO-GND

XGND

6

PMCprotego D

X4A/B

STO1-ENABLE

5

STO2-ENABLE

24 V DC

This manual is related to the following products: