beautypg.com

6wiring – Pilz PSENvip RL D P User Manual

Page 78

background image

6.1

Notes on wiring

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-2

Verdrahtung_Hinweise_EMV

EMC

Avoid interference (e.g. from motors, power lines) by laying cables in
a way that is EMC-compliant.

Verdrahtung_Hinweise_Eingaenge_des_Empfaengers

Inputs on the receiver

The inputs Protected field mode 1/Protected field mode 2 are safe-
ty-related.
– The CNC or safety system provides the signal. It is only absolutely

necessary to connect the inputs to a safety system if communica-
tion is needed for tool detection.

– When driven via relay contacts it is the user's responsibility to apply

an appropriate safety concept.

The inputs for protected field mode 1 and protected field mode 2 can
be switched directly via the 24 VDC supply. In this case, both inputs
should be linked. Only the following protected field modes are pos-
sible:

– "Standard" protected field mode (switch open, both inputs = "0")
– "Box bending with back gauge" protected field mode (switch

closed, both inputs = "1")

Fig. 6-1:

Protected field mode 1/2 directly at the 24 V DC supply

The input to acknowledge the specified protected field mode can be
switched directly via the 24 VDC supply.

Verdrahtung_Hinweise_Funktionspruefung

NOTICE
The acknowledgement button for the protected field mode must
be positioned outside the danger zone in such a way that the
operator can see all of the danger zone.

Protected field mode 2

Protected field mode 1

X1

3

4

24 V DC