7.5
Setting the parameters for bending angle measurement
7
Commissioning
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-24
Parameters for ANGLE 1 to ANGLE 5
ACTIVE
/ INACTIVE
Default setting: INACTIVE
ANGLE 1
to 5
Value range: 0.1 ... 180°, in 0.1° steps
Default setting: 90.0°
MARGIN
Value range: 0.1 ... 10°, in 0.1° steps
Default setting: 1.0
Parameter for ACCURACY
LEVEL
Value range: 1 ... 10
Default setting: 5
The TIME and VALUES parameters cannot be set. They are only dis-
played. Their value depends on the LEVEL parameter.
Value ranges:
TIME
: 20 ... 1800 ms
VALUES
: 1 ... 160
Default setting at LEVEL 5:
TIME
: 450 ms
VALUES
: 40