The PSENvip continuously carries out self-tests and output tests during
operation. If an error is discovered, the following sequence is triggered:
An error identifier is shown on the display of the PSENvip receiver (see
"Error messages" in this chapter)
The error plus some additional diagnostic data is entered in a special
data area on the PSENvip (see "DIAGNOSTICS menu" in this chapter)
Execution of the error reaction.
The PSENvip's reaction to an error depends on the severity of that error.
9.1.1
Minor errors
Minor errors
9-
Diagnose_Fehlerbehandlung_leichte_Fehler
Possible causes
Feasibility error
Internal error
Reaction of the PSENvip
The PSENvip switches to a HOLD state.
Outputs OSSD1/OSSD2 on the receiver are switched off.
In this state it is possible to make adjustments during initial commis-
sioning and after a tool change.
Remedy
Note the error message (see section entitled "Error messages").
Rectify the error.
Press the
ATION state.
9.1.2
Major errors
Major errors
9-
Diagnose_Fehlerbehandlung_schwere_Fehler
Possible causes
Serious internal error
Wiring error, short across contacts, short circuit
No valid tool data
Overrun not entered
Fault on the optical system
Reaction of the PSENvip
The PSENvip switches to a STOP state.
Outputs OSSD1/OSSD2 on the receiver are switched off.
In this state, operation is no longer possible. However, diagnostics
are available.