Troubleshooting

9

Diagnostics and Troubleshooting

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

9-2

9.1

Troubleshooting

9100

Troubleshooting

9-

Diagnose_Fehlerbehandlung_Allg

The PSENvip continuously carries out self-tests and output tests during
operation. If an error is discovered, the following sequence is triggered:

An error identifier is shown on the display of the PSENvip receiver (see
"Error messages" in this chapter)

The error plus some additional diagnostic data is entered in a special
data area on the PSENvip (see "DIAGNOSTICS menu" in this chapter)

Execution of the error reaction.

The PSENvip's reaction to an error depends on the severity of that error.

9.1.1

Minor errors

Minor errors

9-

Diagnose_Fehlerbehandlung_leichte_Fehler

Possible causes

Feasibility error

Internal error

Reaction of the PSENvip

The PSENvip switches to a HOLD state.

Outputs OSSD1/OSSD2 on the receiver are switched off.

In this state it is possible to make adjustments during initial commis-
sioning and after a tool change.

Remedy

Note the error message (see section entitled "Error messages").

Rectify the error.

Press the key and return the PSENvip to the NORMAL OPER-
ATION state.

9.1.2

Major errors

Major errors

9-

Diagnose_Fehlerbehandlung_schwere_Fehler

Possible causes

Serious internal error

Wiring error, short across contacts, short circuit

No valid tool data

Overrun not entered

Fault on the optical system

Reaction of the PSENvip

The PSENvip switches to a STOP state.

Outputs OSSD1/OSSD2 on the receiver are switched off.

In this state, operation is no longer possible. However, diagnostics
are available.