7.4

Enter overrun

7

Commissioning

7.4

Enter overrun

7400

Enter overrun

7-

Inbetriebnahme_Nachlaufweg_eingeben

The max. overrun is a press brake variable that will depend on the ma-
chine type. Once the closing movement has stopped, the max. overrun
must not be exceeded.

The overrun is entered during configuration via the keypad on the
PSENvip receiver.

To enter the overrun, follow the instructions below:

Switch off the voltage to the PSENvip.

Press the + keys and keep them held down.

Switch on the supply voltage again.

Release the + keys when Password? appears on
the display.

Enter the password within 10 s.

To do this, press the following keys in the specified sequence: 1.

,

2.

, 3. , 4. .

The menu for entering the overrun will appear.

NOTICE
The overrun may only be entered by the press brake manufac-
turer or suitably authorised persons.

WARNING!
The value you enter as the overrun must correspond to the value
stated by the manufacture on the press brake's type label!
If you enter a lower value for the overrun, the protected field will
also be reduced to an unpermitted level.
Failure to comply

could result in a hazardous situation, which

could lead to serious injury and death.

INFORMATION
The PSENvip will need to be restarted if the entry
- Was invalid
- Took longer than 10 s.