Converting analog data, Converting analog input data – Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual

Page 97

background image

Using Analog

5–5

Converting Analog Data

The analog input circuits are able to monitor current and voltage signals and convert
them to digital data. There are six terminals assigned to the input channels that
provide two voltage inputs, two current inputs and two return signals (commons).

The analog outputs can support either a current or voltage function. There are three
terminals assigned to the output channels that provide one voltage output, one
current output and a common (shared) terminal.

The following table shows sample Analog Signal and Data Word values using the
nominal transfer function formula:

N=I

in

x 32767/21 where I

in

(analog signal) is in milliamperes (mA)

N=V

in

x 32767/10.5 where Vin (analog signal) is in volts (V)

N=(I

out

– 4 mA) x 32767/16 mA where I

out

(analog signal) is in

milliamperes (mA)

N=V

out

x 32767/10V where V

out

(analog signal) is in volts (V)

Analog Signal

Data Word

Input

Output

0V

0

0

5V

15603

16384

10V

31207

32767

4 mA

6241

0

11 mA

17164

14336

20 mA

31207

32767

Converting Analog Input Data

Analog inputs convert current and voltage signals into 16-bit two’s complement

binary values. To determine an approximate voltage that an input value

represents,

use one of the equations shown on the following page.