Using Data Handling Instructions

9–5

Convert from BCD (FRD)

Use this instruction to convert BCD values to integer values.

The source parameter can be a word address in a data file, or it can be the math
register, S:13. The destination must be a word address.

Updates to Arithmetic Status Bits

With this Bit:

The Controller:

S:0/0

Carry (C)

always resets.

S:0/1

Overflow (V)

sets if non-BCD value is contained at the source or the value
to be converted is greater than 32,767; otherwise reset. On
overflow, the minor error flag is also set.

S:0/2

Zero (Z)

sets if destination value is zero.

S:0/3

Sign (S)

always resets.

Note

Always provide ladder logic filtering of all BCD input devices prior to performing
the FRD instruction. The slightest difference in point-to-point input filter delay can
cause the FRD instruction to overflow due to the conversion of a non-BCD digit.

]/[

S:1

15

EQU

EQUAL
Source A

N7:1

0

Source B

I:0.0

0

MOV

MOVE
Source

I:0.0

0

Dest

N7:1

0

FRD

FROM BCD
Source

I:0.0

0000

Dest

N7:2

0

The two rungs shown cause the controller to verify that the value I:0 remains the
same for two consecutive scans before it will execute the FRD. This prevents the
FRD from converting a non-BCD value during an input value change.

Programming

Execution Times

(

µ

sec) when:

True

False

56.88

5.52

FRD

FROM BCD
Source

Dest