Programming – Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual
Page 259
Using the Message Instruction
13–11
Error
Code
Description of Error Condition
02H
Target node is busy.
03H
Target node cannot respond because message is too large.
04H
Target node cannot respond because it does not understand the command parameters OR
the control block may have been inadvertently modified.
05H
Local processor is offline (possible duplicate node situation).
06H
Target node cannot respond because requested function is not available.
07H
Target node does not respond.
08H
Target node cannot respond.
09H
Local modem connection has been lost.
0AH
Buffer unavailable to receive SRD reply.
0BH
Target node does not accept this type of MSG instruction.
0CH
Received a master link reset.
10H
Target node cannot respond because of incorrect command parameters or unsupported
command.
15H
Local channel configuration parameter error exists.
18H
Broadcast (Node Address 255) is not supported.
1AH
➀
Target node cannot respond because another node is file owner (has sole file access).
1BH
➀
Target node cannot respond because another node is program owner (has sole access to
all files).
37H
Message timed out in local processor.
39H
Message was discarded due to a communication protocol switch.
3AH
Reply from target is invalid.
50H
Target node is out of memory.
60H
Target node cannot respond because file is protected.
E7H
Target node cannot respond because length requested is too large.
EBH
Target node cannot respond because target node denies access.
ECH
Target node cannot respond because requested function is currently unavailable.
FAH
Target node cannot respond because another node is file owner (has sole file access).
FBH
Target node cannot respond because another node is program owner (has sole access to
all files).
➀
Error codes 1A and 1B valid for Series C discrete only.
Note
For 1770–6.5.16 DF1 Protocol and Command Set users:
The MSG error code reflects the STS field of the reply to your MSG instruction.
Codes E0 – EF represent EXT STS codes
0 – F. Codes F0 – FC represent EXT STS codes 10 – 1C.
Programming