MicroLogix 1000 Programmable Controllers User Manual

1–6

The following illustrations show the Master Control Relay wired in a grounded
system.

Note

The illustrations only show output circuits with MCR protection. In most
applications input circuits do not require MCR protection; however, if you need to
remove power from all field devices, you must include MCR contacts in series with
input power wiring.

Schematic (Using IEC Symbols)

X1

230V ac

230V ac

Disconnect

L1

L2

Isolation
Transformer

Operation of either of these contacts will
remove power from the adapter external I/O
circuits, stopping machine motion.

MCR

MCR

MCR

Emergency-Stop
Push Button

Overtravel
Limit Switch

Stop

Start

Suppr.

MCR

(Lo)

(Hi)

Line Terminals: Connect to 230V ac
terminals of Power Supply.

dc Power Supply.
Use IEC 950/EN 60950

MCR

+

X2

Line terminals: Connect to 24V dc
terminals of Power Supply.

24V dc
I/O Circuits

230V ac
I/O Circuits

230V ac
I/O Circuits

Master Control Relay (MCR)
Cat. No. 700-PK400A1

Fuse

Fuse

Suppressor
Cat. No. 700-N24