Troubleshooting Your System

14–3

When an Error Exists

If an error exists within the controller, the controller LEDs operate as described in
the following tables.

The

Following

Error Exists

Probable Cause

Recommended Action

No input

No Line Power

Verify proper line voltage and connections to the
controller.

power or
power supply
error

Power Supply
Overloaded

This problem can occur intermittently if power
supply is overloaded when output loading and
temperature varies.

The

Following

Error Exists

Probable Cause

Recommended Action

Hardware
f

Processor Memory
Error

Cycle power. Contact your local Allen-Bradley
representative if the error persists.

faulted

Loose Wiring

Verify connections to the controller.