Application Examples that Use the MSG Instruction

Example 1

Application example 1 shows how you can implement continuous operation of a
message instruction.

Bit S:0/11 ensures that the MSG instruction will only be processed when
the active protocol is DH-485. Bit S:1/7 ensures that DH-485 is
communicating before sending the MSG. Bit B3/1 enables the MSG
instruction. When the MSG instruction done bit (N7:0/13) is set, it unlatches
the MSG enable bit (N7:0/15) so that the MSG instruction will be
re-enabled in the next scan. This provides continuous operation.

The MSG error bit will also unlatch the enable bit. This provides continuous
operation even if an error occurs.

] [