beautypg.com

Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual

Page 71

background image

Connecting the System

3–13

1761-CBL-PM02

1761-CBL-AP00

Cable

Length

Connections from

to AIC+

External

Power Supply

Required

Power Selection

Switch Setting

1761-CBL-AP00

45 cm (17.7 in)

2

6 f

SLC 5/03 or SLC 5/04 processors, channel 0

port 2

yes

external

76 C

00

1761-CBL-PM02

c

7 7

2m (6.5 ft)

MicroLogix 1000

port 1

yes

external

PanelView 550 through NULL modem adapter

port 2

yes

external

DTAM Plus / DTAM Micro

port 2

yes

external

PC COM port

port 2

yes

external

user supplied cable

Cable

Length

Connections from

to AIC+

External

Power Supply

Required

Power Selection

Switch Setting

straight 9–25 pin

––

modem or other communication device

port 1

yes

external

External power supply required unless the AIC+ is powered by the device connected to port 2, then
the selection switch should be set to cable.

Series B or higher cables are required for hardware handshaking.