Using Data Handling Instructions

9–21

Not (NOT)

The source value is NOTed bit by bit and then stored in the destination (one’s
complement).

Truth Table

Dest = NOT A

A

Dest

0

1

1

0

The source and destination must be word addresses.

Updates to Arithmetic Status Bits

With this Bit:

The Controller:

S:0/0

Carry (C)

always resets.

S:0/1

Overflow (V)

always resets.

S:0/2

Zero (Z)

sets if result is zero; otherwise resets.

S:0/3

Sign (S)

sets if result is negative (most significant bit is set); otherwise
resets.

Programming

Execution Times

(

µ

sec) when:

True

False

28.21

6.92

NOT

NOT
Source

Dest