Using High-Speed Counter Instructions

12–9

When a high preset is reached, no counts are lost.

Hardware and instruction accumulators are reset.

Instruction high preset is loaded to the hardware high preset.

If the DN bit is not set, the DN bit is set. The IH bit is also set and the IL, IV,
and IN bits are reset.

If the DN bit is already set, the OV bit is set. The IV bit is also set and the IL,
IV and IN bits are reset.

High-speed counter interrupt file (program file 4) is executed if the interrupt is
enabled.

The following tables summarize what the input state must be for the corresponding
high-speed counter action to occur:

Up Counter

Input State

H g -Speed

Input Count

(I/O)

Input

Direction

(I/1)

Input Reset

(I/2)

Input Hold

(I/3)

HSC Rung

High-Speed

Counter Action

Turning
Off-to-On

NA

NA

NA

True

Count Up

NA

NA

NA

NA

False

Hold Count

Off, On, or
Turning Off

NA

Off, On, or
Turning Off

NA

NA

Hold Count

NA (Not Applicable)

Programming