Using Math Instructions

8–13

The following example takes a 0V to 10V analog input from a MicroLogix 1000
analog controller and scales the raw input data to a value between 0 and 100%. The
input value range is 0V to 10V which corresponds to 0 to 31,207 counts. The scaled
value range is 0 to 100 percent.

Application Example – Convert Voltage Input to Percent

Scaled Value

(percent)

Input Value

0V

31,207 10V

100

(Scaled Max.)

(Scaled Min.)

(Input Min.)

(Input Max.)

0

Calculating the Linear Relationship

Use the following equations to calculate the scaled units:

Scaled value = (input value x rate)

+

offset

Rate = (scaled max. – scaled min.) / (input max. – input min.)

= (100 –

0) / (31,207 –

0

)

= .00320 (or 32/10000)

Offset = scaled min. – (input min. x rate)

= 0

(0

Ч

.00320)

=

0