Understanding the Communication Protocols

D–11

DH-485 Communication Protocol

The information in this section describes the DH-485 network functions, network
architecture, and performance characteristics. It will also help you plan and operate
the MicroLogix 1000 on a DH-485 network.

Note

Only Series C or later MicroLogix 1000 discrete controllers and all MicroLogix
1000 analog controllers support the DH-485 network.

DH-485 Network Description

The DH-485 protocol defines the communication between multiple devices that
co-exist on a single pair of wires. This protocol uses RS-485 half-duplex as its
physical interface. (RS-485 is a definition of electrical characteristics; it is not a
protocol.) RS-485 uses devices that are capable of co-existing on a common data
circuit, thus allowing data to be easily shared between devices.

The DH-485 network offers:

interconnection of 32 devices

multi-master capability

token passing access control

the ability to add or remove nodes without disrupting the network

maximum network length of 1219 m (4000 ft)

The DH-485 protocol supports two classes of devices: initiators and responders.
All initiators on the network get a chance to initiate message transfers. To
determine which initiator has the right to transmit, a token passing algorithm is used.

The following section describes the protocol used to control message transfers on
the DH-485 network.