beautypg.com

Referencereference – Rockwell Automation 1761 MicroLogix 1000 Programmable Controllers User Manual

Page 307

background image

ReferenceReference

Programming Reference

B–19

Address

Description

Classification

Bit

S:15H

DF1 Baud
Rate

Status

This byte value contains a code used to select
the baud rate of the processor on the DF1 link.
The controller baud rate options are:

300

600

1200

2400

4800

9600 (default)

19200

38400

To change the baud rate from the default value
you must use a programming device.

S:16L

DH-485
Node
Address

Status

This byte value contains the node address of
your processor on the DH-485 link. Each device
on the DH-485 link must have a unique address
between the decimal values 1–31. To change a
processor node address, you must use a
programming device.

S:16H

DH-485
Baud Rate

Status

This byte value contains the baud rate of the
processor on the DH-485 link.
The controller baud rate options are:

9600

19200 (default)

To change the baud rate from the default value,
you must use a programming device.

S:17 to
S:21

Reserved

NA

NA

S:22

Maximum
Observed

c

Dynamic
Configuration

This word indicates the maximum observed
interval between consecutive program cycles.

b

Scan Time

C f

This value indicates, in 10 ms increments, the
time elapsed in the longest program cycle of the
controller. Refer to S:3L for more information
regarding the program cycle. The controller
compares each last scan value to the value
contained in S:22. If the controller determines
that the last scan value is larger than the value
stored at S:22, the last scan value is written to
S:22.

Resolution of the maximum observed scan time
value is

+

0 to

10 ms. For example, the value 9

indicates that 80–90 ms was observed as the
longest program cycle.

Interrogate this value if you need to determine or
verify the longest scan time of your program.