High-Speed Counter Reset Accumulator (RAC)

This instruction allows you to write a specific value to the hardware accumulator
and image accumulator.

The Counter referenced by this instruction has the same address as the HSC
instruction counter and is fixed at C5:0.

Entering Parameters

Enter the following parameter when programming this instruction:

Source represents the value that is loaded to the accumulator. The source can
be a constant or an address.

Operation

Execution of the RAC:

removes pending high-speed counter interrupts

resets the PE, LS, OV, UN, and DN status bits

loads a new accumulator value to the hardware and instruction image

loads the instruction high preset to the hardware high preset (if the high-speed
counter is configured as an Up Counter)

resets the IL, IH, IN, or IV status bits

The source can be a constant or any integer element in files 0–7. The hardware and
instruction accumulators are updated with the new accumulator value immediately
upon instruction execution.

You can have more than one RAC instruction per program referencing the same
source or different sources.

Execution Times

sec

)

when:

True

False

56.00

6.00

RAC

RESET TO ACCUM VALUE
Counter

C5:0

Source