Timer On-Delay (TON)

Use the TON instruction to delay the turning on or off of an output. The TON
instruction begins to count timebase intervals when rung conditions become true.
As long as rung conditions remain true, the timer increments its accumulated value
(ACC) each scan until it reaches the preset value (PRE). The accumulated value is
reset when rung conditions go false, regardless of whether the timer has timed out.

Using Status Bits

This Bit

Is Set When

And Remains Set Until One

of the Following

Timer Done Bit DN (bit 13)

accumulated value is equal
to or greater than the preset
value

rung conditions go false

Timer Enable Bit EN (bit 14)

rung conditions are true

rung conditions go false

Timer Timing Bit TT (bit 15)

rung conditions are true and
the accumulated value is less
than the preset value

rung conditions go false or
when the done bit is set

When the controller changes from the REM Run or REM Test mode to the
REM Program mode or user power is lost while the instruction is timing but has not
reached its preset value, the following occurs:

Timer Enable (EN) bit remains set.

Timer Timing (TT) bit remains set.

Accumulated value (ACC) remains the same.

On returning to the REM Run or REM Test mode, the following can happen:

Condition

Result

If the rung is true:

EN bit remains set.
TT bit remains set.
ACC value is reset.

If the rung is false:

EN bit is reset.
TT bit is reset.
ACC value is reset.