Important DH-485 Network Planning Considerations

Carefully plan your network configuration before installing any hardware. Listed
below are some of the factors that can affect system performance:

amount of electrical noise, temperature, and humidity in the network
environment

number of devices on the network

connection and grounding quality in installation

amount of communication traffic on the network

type of process being controlled

network configuration

The major hardware and software issues you need to resolve before installing a
network are discussed in the following sections.

Hardware Considerations

You need to decide the length of the communication cable, where you route it, and
how to protect it from the environment where it will be installed.

When the communication cable is installed, you need to know how many devices
are to be connected during installation and how many devices will be added in the
future. The following sections will help you understand and plan the network.

Number of Devices and Length of Communication Cable

You must install an AIC+ Advanced Interface Converter, catalog number
1761-NET-AIC, for each node on the network. If you plan to add nodes later,
provide additional advanced interface converters during the initial installation to
avoid recabling after the network is in operation.

The maximum length of the communication cable is 1219 m (4000 ft). This is the
total cable distance from the first node to the last node on the network.