Using Data Handling Instructions

9–7

Clearing S:14 before executing the FRD instruction is shown below:

CLR

CLEAR
Dest

S:14

0

FRD

FROM BCD
Source

S:13

00001234

Dest

N7:0
1234

MPS displays S:13
and S:14 in BCD.

MOV

MOVE
Source

N7:2
4660

Dest

S:13
4660

] [

I:0

1

0001 0010 0011 0100

0000 0100 1101 0010

When the input condition I:0/1 is set (1), a BCD value (transferred from a 4-digit
thumbwheel switch for example) is moved from word N7:2 into the math register.
Status word S:14 is then cleared to make certain that unwanted data is not present
when the FRD instruction is executed.

Programming