Preface

MicroLogix 1000 Programmable Controllers User Manual

B–4

Address

Description

Classification

Bit

S:0/2

Zero

Status

This bit is set by the controller when the result
of certain math or data handling instructions is
zero. Otherwise the bit remains cleared.
When a STI, high-speed counter, or Fault
Routine interrupts normal execution of your
program, the original value of S:0/2 is restored
when execution resumes.

S:0/3

Sign

Status

This bit is set by the controller when the result
of certain math or data handling instructions is
negative. Otherwise the bit remains cleared.
When a STI, high-speed counter, or Fault
Routine interrupts normal execution of your
program, the original value of S:0/3 is restored
when execution resumes.

S:0/4 to
S:0/7

Reserved

NA

NA

S:0/8

Extend I/O
Configuration

Static
Configuration

This bit must be set by the user when unused
outputs are written to. If reset and unused
outputs are turned on the controller will fault
(41H).

S:0/9

Reserved

NA

NA

S:0/10

Primary
Protocol

Static
Configuration

This bit defines the protocol that the controller
will initially use when attempting to establish
communication, where:
0 = DF1 (default setting)
1 = DH-485

S:0/11

Active
Protocol

Status

This bit is updated by the controller during a
protocol switch. It indicates which protocol is
currently being used for communication,
where:
0 = DF1
1 = DH-485

S:0/12

Selected DF1
Protocol

Status

This bit allows the user to determine which
DF1 protocol is configured, where:
0 = DF1 Full-Duplex (default setting)
1 = DF1 Half-Duplex Slave

S:0/13 to
S:0/15

Reserved

NA

NA

Valid for Series A–C discrete only.