Page 287: Q 2/0, Q 2/0 features, Technical characteristics
15
.
22
Power
Distribution
Han-Power
®
T with 3x Han
®
Q 2/0
Features
• Per 1 connection for power input, power output
and to device
• 2 power contacts
• Plastic housings are integrated in the moulding
• Compact design
Current carrying capacity
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which flow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to
DIN EN 60 512-5-2
Operating
current
Ambient temperature
Wire gauge:
6 mm²
Technical characteristics
Specifications
DIN EN 61 984
DIN EN 60 664-1
Han-Power
®
T
Number of contacts
- Power contacts
2 + PE
Electrical data
acc. to EN 61 984
Power side
40 A 400 V 6 kV 3
Rated current
40 A
Rated voltage
400 V
Rated impulse voltage
6 kV
Pollution degree
3
Rated voltage
acc. to UL/CSA
600 V
Insulation resistance
≥ 10
10
Ω
Material
polycarbonate
Limiting temperatures
-40 °C ... +125 °C
Flammability acc. to UL 94
V 0
Mechanical working life
- mating cycles
≥ 500
Degree of protection acc. to DIN EN 60 529 IP 65 / IP 67
Contacts
Material
copper alloy
Surface
- hard-silver plated
3 µm Ag
Contact resistance
≤ 1 mΩ
Crimp terminal
- mm²
2.5 ... 10 mm²
- AWG
14 ... 8