14 . 20 han, Hc modular 650 current carrying capacity, Technical characteristics – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual
Page 247

Han HC
Modular
14
.
20
Han
®
HC Modular 650
Current carrying capacity
Current carrying capacity
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which flow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to
DIN EN 60 512-5-2
Operating current
Ambient temperature
➀ Wire gauge 70 mm²
➁ Wire gauge 95 mm²
➂ Wire gauge 120 mm²
➃ Wire gauge 150 mm²
➄ Wire gauge 185 mm²
➅ Wire gauge 240 mm²
with cable SHXAFO1x240, 4 kV
Technical characteristics
Specifications
DIN EN 60 664-1
DIN EN 61 984
Approvals
Inserts
Number of contacts
1, 2
Electrical data
acc. to EN 61 984
650 A 4000 V 18 kV 3
Rated current
650 A
Rated voltage
4000 V
Rated impulse voltage
18 kV
Pollution degree
3
Insulation resistance
≥ 10
10
Ω
Material
polyamide
Limiting temperatures
-40 °C ... +125 °C
Flammability acc. to UL 94
V 0
Mechanical working life
- mating cycles
≥ 500
Contacts
Material
copper alloy
Surface
silver
Contact resistance
≤ 0.2 mΩ
Axial screw termination
- Wire gauge
1)
70 ... 185 mm²
- MCM
138 ... 350
- Stripping length
23 ... 25 mm
- Max. cable diameter
26.5 mm
- Tightening torque
mm
2
70 95 120 150 185
Nm 12 14 16 17 18
Screw terminal
- Thread
- Tightening torque
M 12
16 ... 18 Nm
Hoods/Housings
For technical details see chapter 31
Frame
Tightening torque
of the fixing screws
0.5 Nm
Material
stainless steel
1)
geometric wire gauge