Han-power, S with 1x han, Q 4/2 with maintenance switch – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual
Page 273: Features technical characteristics han-power, S with 1 x han, Assembly details, Current carrying capacity base element

15
.
08
Power
Distribution
Features
Technical characteristics
Han-Power
®
S with 1 x Han
®
Q 4/2 with Maintenance Switch
• 6 IDC‘s + PE for 4.0 mm² to 6.0 mm² wires
• No interruption of the energy supply
• Space-saving and compact design
• Leading protective ground within the insert
• Assembly with standard tools
•
Line breakout switch
Assembly Details
Specifications
DIN EN 61 984
DIN EN 60 664-1
IEC 61 429-2
Han-Power
®
S
Number of contacts
- Power contacts
4 + PE
- Signal contacts 2
Electrical data
acc. to EN 61 984
Power side
Supply to connector
5 A 230/400 V 4 kV 2
Rated current
5 A
Rated voltage conductor - ground
230 V
Rated voltage conductor - conductor 400 V
Rated impulse voltage
4 kV
Pollution degree
2
Frequency
50 Hz
Energy bus
40 A 230/400 V 4 kV 2
Signal side
10 A 250 V 4 kV 2
Rated current
10 A
Rated voltage
250 V
Rated impulse voltage
4 kV
Pollution degree
2
Rated voltage
acc. to UL/CSA
600 / 250 V
Material
polycarbonate
Limiting temperatures
-25 °C ... +55 °C
Flammability acc. to UL 94
V 0
Mechanical working life
- mating cycles
≥ 500
- Switching cycles
≥ 50.000
Degree of protection acc. to DIN EN 60 529 IP 65
Cables
Design of conductor acc. to
DIN VDE 0281
DIN EN 60 228
Wire gauge
4 mm²
- Number of single strands
56 x 0.3 mm ∅
- Outer diameter
4.2 mm
Wire gauge
6 mm²
- Number of single strands
84 x 0.3 mm ∅
- Outer diameter
4.8 mm
Technical data of switches
Electrical data acc. to IEC/EN 61058-1 (VDE 0630 sect. 1)
for switch-disconnectors
Rated voltage
250 V~ / 400 V~
Rated current
16 (10) A / 10 (5) A
Han
®
Q 4/2 fully loaded
with wire gauge 4 x 6 mm²
➀ Han
®
Q 4/2 Wire gauge: 4 mm²
➁ Han
®
Q 4/2 Wire gauge: 6 mm²
Ambient temperature
Operating
current
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which flow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to DIN EN 60 512-
5-2
The Han-Power
®
S connector is suitable for the assembly of
serial power bus. Having assembled the energy supply
Han-Power
®
S can be inserted at any place along the power
cable. The cable jacket has to be removed, the conductor is
placed without interruption in the IDC.
Han-Power
®
S is suitable for cables with single strands
manufactured acc. to DIN VDE 0281/ DIN EN 60 228 with wire
gauges of 4.0 mm² to 6.0 mm². For the distribution of the device
Han-Compact
®
hoods or cable to cable housings are used.
This power supply can be used with Han-Compact
®
hood.
Current carrying capacity base element