Han® k 4/4, K 4/4, K 4/4 features – Northern Connectors Harting HAN Industrial Rectangular Connectors User Manual
Page 118: Technical characteristics
05
.
06
Han
Com
Han
®
K 4/4
Features
• Combination of power area and signal area in the
same connector
• Axial screw termination for power area
• Cage clamp termination for signal area
• Finger safe
• Same range of wire gauge for PE contact and
power contacts
Assembly instructions see page 05.22
Current carrying capacity
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which flow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to
DIN EN 60 512-5-2
Operating current
Ambient temperature
Wire gauge:
➀ 16 mm²
➁ 22 mm²
Technical characteristics
Specifications
DIN EN 60 664-1
DIN EN 61 984
Approvals
Inserts
Number of contacts
4 / 4 + PE
Electrical data
acc. to EN 61 984
Power area
63 A 690 V 8 kV 3
Rated current
63 A
Rated voltage
690 V
Rated impulse voltage
8 kV
Pollution degree
3
Signal area
16 A 250 V 4 kV 3
Rated current
16 A
Rated voltage
250 V
Rated impulse voltage
4 kV
Pollution degree
3
Rated voltage
acc. to UL
600 V / 230 V
Insulation resistance
≥ 10
10
Ω
Material polycarbonate
Limiting temperatures
-40 °C ... +125 °C
Flammability acc. to UL 94
V 0
Mechanical working life
- mating cycles
≥ 500
Contacts
Power contacts
Material
copper alloy
Surface
- hard-silver plated
3 µm Ag
Contact resistance
≤ 0.5 mΩ
Axial screw termination
- geometric wire gauge
6 ... 22 mm²
- AWG
8 ... 4
Max. insulation diameter
6 ... 16 mm²
8.9 mm
22 mm²
11 mm
Tightening tourque
mm² 6 10 16 22
Nm 2
3
4
4
Stripping length
mm² 6 10 16 22
mm 11
+1
11
+1
11
+1
13
+1
Signal contacts
Material
copper alloy
Surface
- hard-silver plated
3 µm Ag
Contact resistance
≤ 3 mΩ
Cage clamp terminal
- geometric wire gauge
0.14 ... 2.5 mm²
- AWG
26 ... 14
Stripping length
7 ... 9 mm
Hoods/Housings
see chapter 31