Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual
Page 52

Remote Infrastructure Management System - Version 1.0 / July 2014
52
www.chatsworth.com
3.4.1.2 Expansion Card “A” Input Configuration
Expansion Card A contains 12 inputs, configurable as analog 4-20mA, 0-5V, 0-10V(analog 0-5V and 0-10V require additional
jumper configuration) or digital NO (cannot be configured as NC), plus 8 form C relay outputs.
While units will vary depending
on individual configurations, inputs for Expansion Card A are typically numbered 1.1-1.12, 2.1-2.12, etc.
This page will be displayed when configuring an input on an Expansion Card A. It is identical to the RIM-1000 Main Board Input
Configuration page—see 3.4.1.1, “Main Card - Input Channels 1-8” on page 44—with the following exceptions:
• The Expansion Card “A” does not except common ground digital inputs. Therefore, the option for Individual Ground Type
(digital input only) is removed.
• Analog 0-5VDC and Analog 0-10VDC options are added to the Input Type. The Expansion Card “A” accepts analog inputs
individually configurable through internal jumpers, as 4-20mA, 0-5VDC or 0-10VDC.
Figure 3.8 Expansion Card A Configuration Page