Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual
Page 48

Remote Infrastructure Management System - Version 1.0 / July 2014
48
www.chatsworth.com
Table 3.3 RIM-1000 Main Board Configuration Options
Option
Description
Low Limit1
Applies only to analog 4-20mA inputs.
The RIM-1000 will record an alarm and send notification when the RIM-1000
calculated value falls below this limit. The Low Limit 1 and Low
Limit 2 are disabled when they are both set to 0.
Low Limit2
Applies only to analog 4-20mA inputs.
The RIM-1000 will record an alarm and send notification when the RIM-1000
calculated value falls below this limit. The Low Limit 1 and Low
Limit 2 are disabled when they are both set to 0. Low Limit 2 will
also activate any designated relays.
Pager Alarms
Use the Configuration>Modem/Phone Numbers/Pagers link to
configure alarm recipients. You can configure up to 15 phone
numbers, and each will go into a numbered slot, 1 - 15.
Then come back to this field and designate up to five recipients who
should be notified when this point goes into alarm. Separate the
recipients’ ID numbers with commas. The RIM-1000 will first dial the
lowest number listed, regardless of the order in which the numbers
are listed.
Enter zero to disable this feature.
Example: If the Alarm dial out string is set to “3, 5, 1, 0, 0,” the RIM-1000
will dial Pager #1, Pager #3 and then Pager #5 when an alarm
occurs. Pager notification will be sent when an input alarms (high
limit 2, high limit 1, low limit 1, low limit 2 is exceeded or the digital
input is in alarm). See 3.4.12, “Modem/Phone Numbers/Pagers” on
page 74 for more information.
Label
Enter a unique name for this input.
Applies to all input types except “Not Configured.”
• For Analog input types, this label is displayed on the RIM-1000 Main Menu
and the Input Configuration Menu. When the input alarms and/or returns to
normal, the label is included in the Alarm History and notification messages.
• For Digital NO and Digital NC inputs, the label is displayed on the RIM-1000
Main Menu, Input Configuration Menu, Alarm History page and in notification
messages only when the device is in alarm.
• For Digital Status inputs, the label is displayed on the RIM-1000 Main Menu
when the input is on. When the input turns on, the label is also included in the
Digital Status History.