Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual
Page 149

Remote Infrastructure Management System - Version 1.0 / July 2014
Chatsworth Products, Inc. (CPI) • 800-834-4969
149
4.8.2
Telnet/COM1 Configuration
The Modbus/SNMP/BACnet/Telnet Master Configuration page allows the user to configure the RIM-1000 Telnet features.
Figure 4.16 Modbus/SNMP/BACnet/Telnet Configuration Page
If you’d like to utilize Telnet communications, configure the following fields:
Table 4.12 Telnet Communications Options
Option
Description
Serial Com 1
Protocol Type
Configures the Serial COM Port 1 (EIA-232 or EIA-485). Select Telnet to activate
Telnet capabilities.
• Telnet: Enables the RIM-1000 to communicate via Serial COM Port1.
Serial Baud Rate
This option sets the Serial COM Port 1 to 1200, 2400 or 9600 Baud. All the devices
connected to the RIM-1000 Serial COM Port 1 must be Set to operate at the same
Baud rate.
Serial Interface Type
Enable the RIM-1000 Modbus to operate on the EIA-485 or EIA-232
COM Port 1.
Telnet Inactivity
Timeout
After this many minutes of inactivity, the RIM-1000 will timeout of Telnet
communication. Set this value in seconds, from 0 - 999.