Chatsworth Products Remote Infrastructure Management (RIM-1000) User Manual
Page 119

Remote Infrastructure Management System - Version 1.0 / July 2014
Chatsworth Products, Inc. (CPI) • 800-834-4969
119
3.5.
History
The History link provides access to a wide variety of logged historical data for the RIM-1000.
3.5.1 Alarm History
Alarm History displays the last 256 alarms captured by the RIM-1000. Alarms are ranked from most recent (top of the list) to
least recent (bottom of the list).
Figure 3.65 Alarm History Page
The following format is used to record each alarm entry:
AH###-ID-Condition-Date Time (Value UOM) Label
• AH### is the alarm entry index.
• ID is the alarm identifier number; see Appendix E, “Alarm ID Reference Tables” on page 189.
• Condition is On, High1, High2, Low1, Low2, or RTN (Returned to Normal).
• Date and Time is the internal date and time stamp of the alarm condition.
• Label is the alarm descriptor, up to 64 characters long.
• Value and Unit of Measure (UOM) is captured for analog channels only. The value recorded is the actual analog value that exceeded
its alarm threshold.
The Alarm History log entries are color-coded as follows:
Table 3.30 Alarm History Log Entries
Color
Description
Red
A Point configured for dial out (pager) is in alarm and is unacknowledged. The
alarm will be red if the point is configured for both pager and email notification.
Orange
A point not configured for dail out (pager) is in alarm and is unacknowledged.
Blue
The alarm has been acknowledged.
Black
The alarm has returned to normal.