Table I.1 Technical Specifications
Power
1U, RIM-1000
24VDC Model: 24VDC (±10%), 1A max. (power supply
included); 48VDC Model: 36-72VDC, 0.5A max
2U, RIM-1000
24VDC Model: 24VDC (±10%), 2.5A max. (power supply
included); 48VDC Model: 36-72VDC, 1.25A max.
Inputs
Analog/Digital
8 Configurable as 4-20mA (12-bit A/D conversion) or Dry
Contact NO/NC (<15mA)
Optional Internal
Temperature/Humidity
±0.5ºF (@ 25ºC), ±4ºF (@ -40º to 185ºF); ±3%RH (@ 20% to 80%RH)
Keypad
Standard 3x4; 3000VAC RMS optically isolated; 20 User Access Codes
(also accessible via phone/DTMF through modem)
Outputs
Relay
2 Dry Contact, Form C, 1A @ 24VDC, 0.5A resistive @ 120VAC
(controllable via user programmable logic)
Sensor/Accessory Power
24VDC (±10%) @ 300mA max. (power for external sensors
and/or devices)